Load Flow Analysis and Short Circuit Faults with the Additional Distributed Generation Wind Turbine 300 Kw atAndalas University
A B S T R A C T
The study of electric power flow analysis (Load Flow) is intended to obtain information about
the flow of power or voltage in an electric power system network. This information is needed
to evaluate the performance of the power system. Electrical power flow problems include
calculating the flow and system voltage at certain terminals or buses. The benefits of this
power flow study are to find out the voltage at each node in the system, to find out whether all
the equipment meets the specified limits to deliver the desired power, and to obtain the
original conditions in the new system planning. This study is divided into two: the analysis of
data when the conditions have not been added wind turbine and after the addition of 300 kW
wind and the Newton-Raphson method will be used in analyzing the power flow of the
electric power system. Based on the results of the tests, it is found that the overall value of
losses for power flow before the addition of DG is 0.031 MW and 0.037 Mvar, for the voltage
drop with the lowest percentage, namely on bus 10 with a percentage of 96.45 for the 0.4 kV
system and the 20 kV system on bus 19 with a percentage of 99.03, the largest% PF load was
in lump 1 with 98.64 and the smallest% PF was in lump7 with a value of 84.92. The short
circuit data value on the 20 kV bus system at Andalas University before the addition of DG
with 3-phase disturbances averaged 13.354 A, 1-phase disturbances averaged 3.521 A, 2-
phase disturbances averaged 11.719 A and 2 ground phases of 12.842 A Whereas for the
value of power flow after the addition of DG in the form of the wind turbine of 300 kW the
overall value of losses is 0.032 MW and 0.042 MvarAR, for the voltage drop with the
percentage for voltage drop with the lowest percentage is bus 10 with a percentage of 96.63
for system 0, 4 kV and a 20 kV system on bus 14 with a percentage of 98.1, the largest% PF
load is in lump 1 with 98.64 and the smallest% PF is in lump7 with a value of 84.92. The
short circuit data value on the 20 kV bus system at Andalas University after the addition of
DG with 3 phase disturbances has an average value of 13.354 A, 1 phase disturbance averages
3.523 A, 2 phase disturbances average 11.737 A and 2 phases ground is 12.059 A For the
source in this system, after the addition of DG, there was a change in the% PF of the PLN
grid, namely 79.53 and the wind turbine -83%.
KEYWORDS
Power Flow Analysis, Short Circuit Analysis,
Distributed Generation, Wind Turbine